General
GRMS planning guideSwitch lookbookLighting controlOccupancy detectionEnergy saverProject timelineProducts
Release notesFleet ManagerCloud API401-D2401-DFor partners
Partner portalGuest room components and datasheets
Standard room layout
Compatible components
Most DALI-2 luminaire drivers, motion sensors, digital input units, and panels that have been manufactured according to the standard are compatible with 401-D2.
However, if you are planning to use a component that is not listed below, please reach out to Mount Kelvin so we can assure compatibility in advance.
Name | Component | Image | Category |
---|---|---|---|
Room control kit | RCK | ||
Master unit | Gateway | ||
BACnet gateway | Gateway | ||
PIR motion sensor / presence detector | SensorDetector | ||
Door sensor | Sensor | ||
1-channel dimmer unit | Driver | ||
1-channel dimmer unit | Driver | ||
1-channel dimmer unit | Driver | ||
1-channel blinds controller | Driver | ||
2-channel blinds controller | Driver | ||
4-channel dimmer unit | Driver | ||
Integrated DALI driver | Depends on manufacturer | Driver | |
Integrated DALI-2 driver | Depends on manufacturer | Driver | |
Power relay unit | Relay | ||
Control relay unit | Relay | ||
1-channel relay unit | Relay | ||
4-channel relay unit | Relay | ||
8-channel relay unit | Relay | ||
DALI-2 panels | Switch | ||
Four scenes switch (wireless) | Switch | ||
Curtain switch (wireless) | Switch | ||
Reading / desk / floor lamp switch (wireless) | Switch | ||
Four scenes switch (wired) | Switch | ||
Curtain switch (wired) | Switch | ||
Reading / desk / floor lamp switch (wired) | Switch |
Please note
- Luminaire manufacturers may also be able to equip pendants with DALI or DALI-2 drivers
- The best practice for connecting floor and table lamps to mains is to use luminaire outlet sockets (traditional or DCL-type)
- Make sure that floor, table, and reading lights are ordered without integrated switches
Technical constraints
DALI bus
- The maximum number of devices is 64
- The maximum length of bus cable is 300 m (1.5 mm cable)
- DALI bus voltage: 12Vā22.5 V (typical 16V)
- Data transfer speed: 1200 baud (asynchronous)
- The DALI power supply provides up to 250 mA for the DALI bus, each device may draw up to 2 mA unless bus-powered.
EnOcean radio
- Frequency 868.300 MHz
- Transmission range 300 m free field, typically 30 m indoor
- Switch power generation by rocker movement via an electro-dynamic power generator
- The number of wireless switches is unlimited